serve a preferred startup date.1.1 Configuration and installation featuresThe 9395 Model IBC-L battery cabinet is designed to e installed in a standalone configuration using up tp two battery cabinets. Power wiring is installed externally b tween each battery cabinet and the UPS or battery disconnect using conduit. Batt
600V. The wiring should be a minimum of 18 AWG rated at 48V, 1 A minimum.All interface w ing between the UPS and battery cabinet is to be provided by the customer.When installing external interface wiring (for example, battery breaker shunt trip) to the battery cabinet interface terminals,
tween each battery cabinet and the UPS or battery disconnect using conduit. Batt ry cabinets may be installed adjacent to the UPS or in a separate location.If the battery cabinet is installed adjacent to the UPS, the recommended installati n location for the battery cabinet is on the right side of the UPS cabi
Battery Cabinet (IBC) systems are housed in single free-standing cabinets. Model IBC-L with a ingle battery voltage range is available to meet application runtime nee s. Up to four cabinets may be installed to further ext nd battery runtimes. The cabinets match the UPS cabinet in style
For the 93PM and 93E product lines, there are two different battery cabinets: Small and Large Battery Cabinet. The battery block configuration in the chosen battery cabinet must always match the UPS requirement. Used battery configuration must be inserted into UPS settings during commissioning or start-up.
ingle battery voltage range is available to meet application runtime nee s. Up to four cabinets may be installed to further ext nd battery runtimes. The cabinets match the UPS cabinet in style and color. Figure 1-1 shows the Powerware 9395 Model IBC-L Battery Cabinet.A DC-rated circ