Until existing model codes and standards are updated or new ones developed and then adopted, one seeking to deploy energy storage technologies or needing to verify an installation’s safety may be challenged in applying current CSRs to an energy storage system (ESS).
The size requirements limit the maximum electrical storage capacity of nonresidential individual ESS units to 50 KWh while the spacing requirements define the minimum separation between adjacent ESS units and adjacent walls as at least three feet.
Discussions with industry professionals indicate a significant need for standards …” [1, p. 30]. Under this strategic driver, a portion of DOE-funded energy storage research and development (R&D) is directed to actively work with industry to fill energy storage Codes & Standards (C&S) gaps.
As cited in the DOE OE ES Program Plan, “Industry requires specifications of standards for characterizing the performance of energy storage under grid conditions and for modeling behavior. Discussions with industry professionals indicate a significant need for standards …” [1, p. 30].
4.0 Energy Storage System Installation Review and Approval The purpose of this chapter is to provide a high-level overview of what is involved in documenting or validating the safety of an ESS as installed in, on, or adjacent to buildings or facilities.
It is recognized that electric energy storage equipment or systems can be a single device providing all required functions or an assembly of components, each having limited functions. Components having limited functions shall be tested for those functions in accordance with this standard.