If the float voltage is set to 2.30V/cell at 25°C (77°F), the voltage should read 2.27V/cell at 35°C (95°F). Going colder, the voltage should be 2.33V/cell at 15°C (59°F). These 10°C adjustments represent 30mV change. Table 3 indicates the optimal peak voltage at various temperatures when charging lead acid batteries.
Lead-acid batteries: A lead-acid battery should come with a smart charger that allows for voltage changes when sensing fluctuating temperature ranges. It should set the voltage higher when the battery is charged at lower temperatures and a lower voltage when charging at higher temperatures.
Lead acid is sluggish and cannot be charged as quickly as other battery systems. (See BU-202: New Lead Acid Systems) With the CCCV method, lead acid batteries are charged in three stages, which are constant-current charge, topping charge and float charge.
Heat is the worst enemy of batteries, including lead acid. Adding temperature compensation on a lead acid charger to adjust for temperature variations is said to prolong battery life by up to 15 percent. The recommended compensation is a 3mV drop per cell for every degree Celsius rise in temperature.
A lead acid battery charges at a constant current to a set voltage that is typically 2.40V/cell at ambient temperature. This voltage is governed by temperature and is set higher when cold and lower when warm. Figure 2 illustrates the recommended settings for most lead acid batteries.
Choosing the Right Charger for Lead-Acid Batteries The most important first step in charging a lead-acid battery is selecting the correct charger. Lead-acid batteries come in different types, including flooded (wet), absorbed glass mat (AGM), and gel batteries. Each type has specific charging requirements regarding voltage and current levels.