tween each battery cabinet and the UPS or battery disconnect using conduit. Batt ry cabinets may be installed adjacent to the UPS or in a separate location.If the battery cabinet is installed adjacent to the UPS, the recommended installati n location for the battery cabinet is on the right side of the UPS cabi
serve a preferred startup date.1.1 Configuration and installation featuresThe 9395 Model IBC-L battery cabinet is designed to e installed in a standalone configuration using up tp two battery cabinets. Power wiring is installed externally b tween each battery cabinet and the UPS or battery disconnect using conduit. Batt
ing between the UPS and battery cabinet is to be provided by the customer.When installing external interface wiring (for example, battery breaker shunt trip) to the battery cabinet interface terminals, conduit must be installed between the battery cabinets and the UPS cabi
The battery cabinet shall feature lightweight, compact, long-life Li-ion batteries, which provide energy to support the load during a momentary loss of input power to the rectifier. The Li-ion battery cabinet shall be white. Front access only for installation, service, and maintenance when there is no seismic requirement.
A set of battery cabinets (or racks) shall be furnished with sufficient kilowatt hour rating to maintain the module rated output for a duration of [ ] minutes at 77°F and with a minimum end cell voltage of 3V. Each battery string shall be housed in a dedicated cabinet. Each string shall consist of [ ] modules of 8 cells.
The Li-ion battery cabinet shall be white. Front access only for installation, service, and maintenance when there is no seismic requirement. Rear clearance during installation to comply with seismic requirements. Each battery cabinet shall feature a DC-rated circuit breaker.