The document provides a commissioning procedure for an HT capacitor bank and reactor. The procedure involves visually inspecting the equipment, checking capacitance and resistance values, testing relays and connections, ensuring proper discharge time for capacitors, and checking reactance values.
Ans: Testing the efficiency and functioning of capacitor banks is known as capacitor bank testing. It involves various types of tests to identify faults in the banks’ functioning. Discover the significance of capacitor bank testing and learn the essential procedures with Schneider Electric. Ensure optimal performance and reliability.
Visually trace the interconnection between individual capacitors, and verify that they as per the drawing. Check the capacitance value of the bank using LRC meter, and compare with the specified value. Check IR values. IF CT or residual VT (RVT) is provided, it has to be tested as per standard testing procedure.
This document provides a standard work practice for testing capacitor banks at electrical substations. It outlines: 1. The purpose and scope of capacitor bank testing 2. Required staffing and training, including a competent engineer and safety observer 3.
An ANSI or IEEE standard is used for testing a capacitor banks. Tests on capacitor banks are conducted in three different ways. These are When a company introduces a new design of power capacitor, the new batch of capacitors must be tested to see if they meet the standards.
Visual Inspection of the Capacitor Bank Conditions Examine the external surfaces & make sure the capacitors & reactors are clean & dry. Check that the primary connections are correct. Check the earthing connections between the capacitor bank mounting frames & enclosure.